[GLB161.1E]





Description

Air Damper Actuator
Rotary version, modulation, AC24V
Electric motor driven actuator, modulation for DC 010V control signal, nominal torque 5/10Nm, AC 24V working voltage, self-adapting to rotation angle range, DC 010V feedback signal for position display, mechanically adjustable operating range 0 to 90°, wired with 0.9m connection cable.
Type-specific variations with adjustable auxiliary switches for offset and span adjustable control signals and auxiliary functions
Uses
To activate air damper in ventilation and air conditioning plants
For connecting controllers with DC 0~10V modulation output signal
Nominal Torque
5 Nm for damper area of about 5 Nm and up to 0.8 square meters
For damper area of approx. 0.4 inches (10 mm), up to 10 Nm (10 Nm)
Type Overview
Operating voltage: AC 24 V.
torque
Control signal
Standard Application
(Offset, Non-Span Adjustable)
No auxiliary switch
10Nm
DC010V
GLB161.1E
Order yours
Auxiliary switch cannot be integrated later. Therefore, please order the type you want with the options you want.
Delivery
Individual parts, such as position indicators and other mounting materials on actuator are shipped individually and require additional installation.
The connection cable actuator comes with a pre-wired connection cable of 0.9 meters.
Equipment Combination
These actuators transmit modulation DC 0-10V signals and connect to all control devices that comply with all relevant safety requirements.
Settings and Operation Elements
Technical Data
Power Supply: AC 24 V.
Operating voltage: AC24V + 20%
Safety Special Low Voltage (SELV) or
Ultra Low Voltage (PELV) Protection Based on 384
Supply line up to 10A
Frequency: 50/60Hz
Power supply (with control signal) 125mA
Power consumption: Control signal included 3 V A/2 W
Holds 1VA/1W
Mechanical Data
Torque GLB16..1E
Nominal Torque 10 Nm
Minimum Retention Torque (with or without working voltage> 10 Nm
<; 14 Nm
Nominal rotation angle (with position display) 90°
Maximum rotation angle (mechanical limit) 95° ± 2°
Motor operation at nominal rotation angle 90°, 50/60 Hz 150 seconds / 125 seconds
The motor on the damper block is 6 seconds every 24 hours.
Rotation direction (defined by DIL switch settings) clockwise / counterclockwise
Input
Control Signal Y
Input Voltage (wire 8-2) DC 010 V
Max. Allowed Input Voltage: DC 35 V
DC 10V Limited
Input Resistance > 100k
Neutral Zone NZ (For Unadjustable Operating Function) 200 mV